Transformateurs / transformers - Current Sense Transformers - FAMILLE 69V30
These current sense transformers are fitted with high-permeability toroidal core (ferrite) and feature
across the secondary (under given conditions) a voltage proportional to the primary current.
They are used as control and protection devices to sense current without any disturbance to the
circuits in SMPS, lighting and UPS equipment.
Types | Code | Turns ratio Pri/Sec | PRI current A | SEC induct mH (Rated) | DC resistance Ω max. | Schem |
69V30 | 69V30 5500 | 1/500 | 5 | 600 | 18 | A |
69V30 A500 | 1/500 | 10 | 600 | 18 | B | |
69V30 B100 | 1/100 | 20 | 20 | 1.4 | B | |
69V30 B200 | 1/200 | 20 | 80 | 4.5 | B | |
69V30 B300 | 1/300 | 20 | 180 | 11 | B | |
69V30 B500 | 1/500 | 20 | 600 | 18 | B |
Rated inductance: at +20°C and 10 kHz, 0.1 mA
Inductance tolerance: +50 -30%
Operating frequency: 20 kHz plus
Current primary peak (1 turn): 20A
Operating temperature: -30 to +125°C
Dielectric strenght Pri/Sec: 4000 Vac
Scale factor with rated terminating resistance: Vout 1V per 1A
Approx. weight: 16 g
The transformers are designed and tested in accordance with EN 138100; EN 60938-1
The cases are of flame-retardant plastic material in accordance with UL 94V-0